SKU: AQUAO401-3-230-120
Price: 4886 UAH
Availability: In stock
Termojet 401N actuator is a compact motorized servo-actuator for 3- and 4-way rotary mixing valves. Supply voltage 230V AC, control type — 3-point (ON/OFF), torque 6 Nm, full travel time 90° — 120 seconds, protection class IP42. Designed for use with boiler controllers that have a standard 3-position open/close output. Power consumption — no more than 5 W.
| Parameter | Value |
|---|---|
| Supply voltage | 230V AC, 50–60 Hz |
| Power consumption | max. 5 W |
| Torque | 6 Nm |
| Control type | 3-point ON/OFF |
| Travel time 90° | 120 sec |
| Protection class | IP42 |
| Noise level | max. 40 dB (at a distance of 100 mm) |
| Cable length | 1 m (3×0.75 mm²) |
| Manual control | Yes (unlock button + handle) |
| Application | 3/4-way valves DN15–DN50 |
| Certificates | CE, RoHS |
The actuator connects to the boiler controller with three wires: common (N), "open" and "close". When 230V AC is applied to one of the control inputs, the motor rotates the shaft in the corresponding direction — the valve moves. When the signal is removed, the shaft stops and holds the current position. The built-in indicator shows the current valve position. The unlock button allows manual rotation of the shaft — convenient during commissioning or an emergency without de-energizing the actuator.
In systems with a heat pump, the 401N actuator can control a mixing valve to maintain the optimal supply temperature to the circuits. If your heat pump has an analog 0–10V output, consider the Termojet 411 actuator (0–10V, 24V) — it provides smoother proportional control for maximum efficiency. Learn more about controlling heating systems with a heat pump on the Termojet heat pumps website.
What is the difference between the 401N and 405N actuators?
Both are 3-point, 230V, 6 Nm. The 401N has a travel time of 120 seconds — for systems requiring smoother, slower control (large circuits, high thermal inertia). The 405N — 60 seconds — for systems requiring faster response.
Does the 401N connect to any boiler controller?
Yes, provided the controller has a standard 3-position open/close output at 230V AC. This is the most common output type for controlling mixing valves. If the controller has an analog 0–10V output or 24V supply — the Termojet 411 is suitable.
| Напруга | 230V AC, 50-60 Гц |
|---|---|
| Енергоспоживання | макс. 5 Вт |
| Крутний момент | 6 Нм (10 Нм на замовлення) |
| Керування | 3-точкове ON/OFF |
| Час обертання 90° | 120 сек |
| Ручне керування | Так (кнопка розблокування + ручка) |
| Клас захисту | IP42 |
| Рівень шуму | макс. 40 дБ (на відстані 100 мм) |
| Довжина кабелю | 1 м (3×0.75 мм²) |
| Сертифікати | CE, RoHS |
| Застосування | 3/4-ходові поворотні клапани DN15–DN50 |